TF2100 Single Phase KWH Meter Tester

TF2100 Single phase KWH meter tester is a desk-top portable energy meter tester applicable to the testing of electronic and electro-mechanical single-phase active or reactive energy meter as well as multi-function energy meter. One to three meters may be connected to this device.

Description

General

TF2100 portable Single phase KWH meter tester is a kind of desk-top portable energy meter testing device which is equipped with a single-phase high-stability program-controlled power source and Single -phase multi-function standard meter developed and manufactured by our company. The device can be operated with keyboard to achieve simple functional tests, or control and management may be realized with personal computer. The PC tester has a complete range of test items and the testing device has such advantages as high measurement accuracy, high long-term stability, high degree of automation, wide output range, low distortion and high stability.

This single phase KWH meter tester is applicable to the testing of electronic and electro-mechanical single-phase active or reactive energy meter as well as multi-function energy meter.

This device can provide you with plenty of electrical information such as AC voltage, AC current, power factor, active power, reactive power, apparent power, frequency and etc.

One to three meters may be connected to this device with built-in or plug-in error processor.

This single phase KWH meter tester can be used for product test in such areas as product development, product maintenance, and production lines. Customer may self-develop its own automatic meter calibration software by making use of the underlying dynamic link library developed by our company.

Technical Specification

1 Electrical output

1.1 Voltage and current measurement range

Output voltage ranges: 57.7V/63.5V and 220V/240V (480V optional)

Output current ranges: 0.1A, 1A, 5A, 20A, and 100A

1.2 Output load capacity

Voltage loop: Max. 50VA

Current loop: Max 100VA (Measurement range 100A)

1.3 Electrical output adjustment

1.3.1 Voltage adjustment

  1. a) Adjustment range: 0%~125% selected voltage range
  2. b) Adjustment fineness: four finenesses as 10%, 1%, 0.1%, and 0.01% are   available
  3. c)   Max. output voltage: 300V or 600V

1.3.2 Current adjustment

a) Adjustment range: 0%~120% selected current range

b) Adjustment fineness: four finenesses as 10%, 1%, 0.1%, and 0.01% are available

c) Max. output current: 120A

1.3.3 Phase adjustment

a) Adjustment fineness: 0°~359.99°

b) Adjustment fineness: four finenesses as 10°, 1°, 0.1°, and 0.01° are available

1.4 Voltage and current output distortion

This device’s voltage and current output distortion will not be more than 0.5% (testing under linear load)

1.5 Output power stability

This device’s pre-set output power will not exceed 0.02% compared with the measurement range variation within 180S.

1.6 Harmonic content

a) Number of harmonic waves: 2~21

b) Harmonic content: less than 40% (compared with fundamental wave)

c) Harmonic phase: 0°~359.99°

1.7 Monitoring instrument

To be read directly from the standard meter.

1.8 Electric pulse

Electric pulse output from standard meter:

1) For error calculator to calculate the error of any meter to be tested;

2) For the reference of upper-level measurement examination and determination agency when sending the standard meter to them for testing. Please refer to standard meter’s Table of Constants for pulse constants.

1.9 Power supply

Single-phase AC 220V/240V (100V/110V is also applicable), 50/60Hz,

max. input power consumption: 500W.

1.10 Dimension: 470*480*200mm